Programming Manual Compact i / iX Series
AMETEK Programmable Power Division 69
CURRent:PROTection:STATe
This command enables or disables the AC source overcurrent (OC) protection function. If the
overcurrent protection function is enabled and the AC source exceeds the programmed level,
then the output is disabled and the Questionable Condition status register OC bit is set (see
Chapter 7). An overcurrent condition can be cleared with OUTPut:PROTection:CLEar after the
cause of the condition is removed.
Use OUTP:PROT:DEL to prevent momentary current limit conditions caused by programmed
output changes from tripping the over current protection. Use CURR:PROT:DEL to hold off
tripping the output due to temporary overload conditions.
Command Syntax
[SOURce:]CURRent:PROTection:STATe<bool>
Parameters 0 | 1 | OFF | ON
*RST Value OFF
Examples CURR:PROT:STAT 0 CURR:PROT:STAT OFF
Query Syntax [SOURce:]CURRent:PROTection:STATe?
Returned Parameters 0 | 1
Related Commands OUTP:PROT:CLE CURR:PROT:DEL