Programming Manual Compact i / iX Series
AMETEK Programmable Power Division 93
VOLTage:SLEW:MODE
Phase Selectable
This command determines how the output voltage slew rate is controlled during a triggered
output transient. The choices are:
FIXed The slew rate is unaffected by a triggered output transient.
STEP The slew rate is programmed to the value set by
VOLTage:SLEW:TRIGgered when a triggered transient occurs.
PULSe The slew rate is changed to the value set by
VOLTage:SLEW:TRIGgered for a duration determined by the pulse
commands.
LIST The slew rate is controlled by the voltage slew list when a triggered
transient occurs.
Command Syntax [SOURce:]VOLTage:SLEW:MODE<mode>
Parameters FIXed | STEP | PULSe | LIST
*RST Value FIX
Examples VOLT:SLEW:MODE LIST VOLT:SLEW:MODE FIX
Query Syntax [SOURce:]VOLTage:SLEW:MODE?
Returned Parameters <CRD>
Related Commands VOLT:SLEW:TRG VOLT:SLEW
VOLTage:SLEW:TRIGgered
Phase Selectable
This command selects the slew rate that will be set during a triggered step or pulse transient. A
parameter of MAXimum or INFinity will set the slew to its maximum possible rate. The SCPI
representation for infinity is 9.9E37.
Command Syntax [SOURce:]VOLTage:SLEW:TRIGgered<NRf+>|INFinity
Parameters 1E-3 to 9.9E37 | INFinity |MINimum | MAXimum
Unit V/S (volts per second)
*RST Value INFinity
Examples VOLT:SLEW:TRIG 1 VOLT:SLEW:TRIG MAX
VOLT:SLEW:TRIG INF
Query Syntax [SOURce:]VOLTage:SLEW:TRIGgered?
Returned Parameters <NR3>
Related Commands VOLT:SLEW:MODE VOLT:SLEW